DevicesHeat Pump
Nibe

Nibe Heatpump F-Series

Supported Devices

Device TypeModbus TCP (Ethernet)RS485
Nibe F-Series Heatpump❌✅
Note
Note

The Modbus 40 communication module is also needed to enable Modbus communication on this heatpump https://www.nibe.eu/nl-nl/producten/accessoires/modbus-40

[!WARNING] Control is only possible using SG-Ready Operation Modes (Boosting or Blocking). Specific Wattage control is not supported. The control is done by using the offset curve of the manufacturer

Connection

The communication between the SmartgridOne Controller and the Nibe F1253 heatpump operates via RS485.

RS485

Info
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
ARS485 ARS485_POSRS485 ATX+
BRS485 BRS485_NEGRS485 BTX-
GND (if available)RS GNDGNDNot availableG